Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA067861R1 | XT2H 160 EKIP LS/I IN=160A 3P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
160A
Number of auxiliary contacts as change-over contact
0
Overload release current setting
64.0 .. 160A
Degree of protection (IP)
IP20
Rated voltage
220 .. 690V
Position of connection for main current circuit
Front side
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
Type of control element
Toggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
With switched-off indicator
Adjustment range undelayed short-circuit release
160 .. 1600A
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
With under voltage release
Adjustment range short-term delayed short-circuit release
160 .. 1600A
Motor drive optional
Complete device with protection unit