

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
- - -A
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated voltage
220 - 690V
Rated permanent current Iu
160A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
With under voltage release
No
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
Yes
Adjustment range undelayed short-circuit release
10 - 100A
Degree of protection (IP)
IP20
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
Motor drive optional
Yes
Number of poles
4
With switched-off indicator
No
Type of control element
Toggle
Complete device with protection unit
Yes
Integrated earth fault protection
No
Motor drive integrated
No
From same serie
1SDA067896R1 | XT2H 160 EKIP I IN=10A 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
- .. -A
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated voltage
220 .. 690V
Rated permanent current Iu
160A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
With under voltage release
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
10 .. 100A
Degree of protection (IP)
IP20
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Position of connection for main current circuit
Front side
Motor drive optional
Number of poles
4
With switched-off indicator
Type of control element
Toggle
Complete device with protection unit
Integrated earth fault protection
Motor drive integrated
From same serie
We use cookies to enhance your experience.