Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA067904R1 | XT2H 160 EKIP LSI IN=63A 4P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
160A
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
25.2 .. 63A
Number of auxiliary contacts as change-over contact
0
Number of poles
4
Position of connection for main current circuit
Front side
Degree of protection (IP)
IP20
Type of control element
Toggle
Adjustment range short-term delayed short-circuit release
63 .. 630A
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
63 .. 630A
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Motor drive optional
Complete device with protection unit
Device construction
Built-in device fixed built-in technique
With under voltage release
Rated voltage
220 .. 690V