Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Device construction
Built-in device fixed built-in technique
With switched-off indicator
No
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
Yes
Rated permanent current Iu
160A
Complete device with protection unit
Yes
Number of poles
3
Type of control element
Toggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range short-term delayed short-circuit release
63 - 630A
Motor drive optional
Yes
Position of connection for main current circuit
Front side
Overload release current setting
25.2 - 63A
Adjustment range undelayed short-circuit release
63 - 630A
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Yes
Rated voltage
220 - 690V
Motor drive integrated
No
With under voltage release
No
From same serie
1SDA067988R1 | XT2V 160 EKIP LSIG IN=63A 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
160A
Complete device with protection unit
Number of poles
3
Type of control element
Toggle
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range short-term delayed short-circuit release
63 .. 630A
Motor drive optional
Position of connection for main current circuit
Front side
Overload release current setting
25.2 .. 63A
Adjustment range undelayed short-circuit release
63 .. 630A
Degree of protection (IP)
IP20
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Rated voltage
220 .. 690V
Motor drive integrated
With under voltage release
From same serie
We use cookies to enhance your experience.