Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA068060R1 | XT3N 250 TMD 63-630 4P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Overload release current setting
44.1 .. 63A
Number of auxiliary contacts as change-over contact
0
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Motor drive optional
With switched-off indicator
Rated voltage
220 .. 690V
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
630 .. 630A
With under voltage release
Adjustment range short-term delayed short-circuit release
- .. -A
Rated permanent current Iu
63A
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Position of connection for main current circuit
Front side
Type of control element
Rocker lever
Complete device with protection unit
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Motor drive integrated