Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
160A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Rated voltage
220 - 690V
Adjustment range undelayed short-circuit release
40 - 400A
Overload release current setting
16.0 - 40A
Adjustment range short-term delayed short-circuit release
40 - 400A
With under voltage release
No
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Front side
Type of control element
Toggle
Motor drive optional
Yes
Degree of protection (IP)
IP20
Number of poles
3
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
No
DIN rail (top hat rail) mounting optional
Yes
With switched-off indicator
No
Complete device with protection unit
Yes
From same serie
1SDA068122R1 | XT4N 160 EKIP LS/I IN=40A 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
160A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Rated voltage
220 .. 690V
Adjustment range undelayed short-circuit release
40 .. 400A
Overload release current setting
16.0 .. 40A
Adjustment range short-term delayed short-circuit release
40 .. 400A
With under voltage release
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Front side
Type of control element
Toggle
Motor drive optional
Degree of protection (IP)
IP20
Number of poles
3
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
DIN rail (top hat rail) mounting optional
With switched-off indicator
Complete device with protection unit
From same serie