Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP20
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Motor drive integrated
Adjustment range short-term delayed short-circuit release
63 .. 630A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Adjustment range undelayed short-circuit release
63 .. 630A
Rated voltage
220 .. 690V
Overload release current setting
25.2 .. 63A
DIN rail (top hat rail) mounting optional
With under voltage release
Rated permanent current Iu
63A
Number of poles
3
Position of connection for main current circuit
Front side
Type of control element
Rocker lever
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Device construction
Built-in device fixed built-in technique
Complete device with protection unit