Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
160A
Rated voltage
220 - 690V
Number of poles
3
With switched-off indicator
No
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Overload release current setting
40.0 - 100A
Degree of protection (IP)
IP20
Motor drive optional
Yes
Complete device with protection unit
Yes
With under voltage release
No
Adjustment range undelayed short-circuit release
100 - 1000A
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
Yes
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Position of connection for main current circuit
Front side
Adjustment range short-term delayed short-circuit release
100 - 1000A
From same serie
1SDA068139R1 | XT4N 160 EKIP LSIG IN=100A 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
160A
Rated voltage
220 .. 690V
Number of poles
3
With switched-off indicator
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Overload release current setting
40.0 .. 100A
Degree of protection (IP)
IP20
Motor drive optional
Complete device with protection unit
With under voltage release
Adjustment range undelayed short-circuit release
100 .. 1000A
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Position of connection for main current circuit
Front side
Adjustment range short-term delayed short-circuit release
100 .. 1000A