Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA068154R1 | XT4N 160 EKIP LSI IN=63A 4P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
36kA
Rated voltage
220 .. 690V
Rated permanent current Iu
160A
Adjustment range undelayed short-circuit release
63 .. 630A
Overload release current setting
25.2 .. 63A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With switched-off indicator
Adjustment range short-term delayed short-circuit release
63 .. 630A
Integrated earth fault protection
Type of control element
Toggle
With under voltage release
Position of connection for main current circuit
Front side
Complete device with protection unit
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP20
Number of poles
4
Motor drive optional
Motor drive integrated