Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Rated permanent current Iu
160A
Rated voltage
220 - 690V
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
With under voltage release
No
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
DIN rail (top hat rail) mounting optional
Yes
Motor drive integrated
No
Type of control element
Toggle
With switched-off indicator
No
Motor drive optional
Yes
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Overload release current setting
11.2 - 16A
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
300 - 300A
From same serie
1SDA068332R1 | XT4H 160 TMD 16-300 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
70kA
Rated permanent current Iu
160A
Rated voltage
220 .. 690V
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
With under voltage release
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
DIN rail (top hat rail) mounting optional
Motor drive integrated
Type of control element
Toggle
With switched-off indicator
Motor drive optional
Position of connection for main current circuit
Front side
Complete device with protection unit
Overload release current setting
11.2 .. 16A
Degree of protection (IP)
IP20
Adjustment range undelayed short-circuit release
300 .. 300A