Aleta.hr
Main Product Image

1SDA068435R1 | XT4S 160 MA 52 IM=260...520 3P F F

Code: 1530833

ManufacturerABB
Catalog number1SDA068435R1
Type
EAN code8015644023416

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)IP20
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact0
Overload release current setting- - -A
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitBolt connection
Rated voltage220 - 690V
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release- - -A
With under voltage releaseNo
Adjustment range undelayed short-circuit release260 - 520A
DIN rail (top hat rail) mounting optionalYes
With switched-off indicatorNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Number of poles3
Rated permanent current Iu52A
Device constructionBuilt-in device fixed built-in technique
Position of connection for main current circuitFront side
Type of control elementRocker lever
Motor drive integratedNo
Integrated earth fault protectionNo
Motor drive optionalYes
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA068435R1 | XT4S 160 MA 52 IM=260...520 3P F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)

IP20

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

0

Overload release current setting

- .. -A

Number of auxiliary contacts as normally open contact

0

Type of electrical connection of main circuit

Bolt connection

Rated voltage

220 .. 690V

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

- .. -A

With under voltage release

Adjustment range undelayed short-circuit release

260 .. 520A

DIN rail (top hat rail) mounting optional

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Number of poles

3

Rated permanent current Iu

52A

Device construction

Built-in device fixed built-in technique

Position of connection for main current circuit

Front side

Type of control element

Rocker lever

Motor drive integrated

Integrated earth fault protection

Motor drive optional

Complete device with protection unit