Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA068472R1 | XT4S 160 EKIP LS/I IN=63A 3P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as change-over contact
0
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
63 .. 630A
Adjustment range undelayed short-circuit release
63 .. 630A
With switched-off indicator
Motor drive optional
Degree of protection (IP)
IP20
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Rated voltage
220 .. 690V
Number of auxiliary contacts as normally open contact
0
Overload release current setting
25.2 .. 63A
With under voltage release
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
63A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Number of poles
3
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
Type of control element
Rocker lever
Complete device with protection unit
Integrated earth fault protection