

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
- - -A
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Adjustment range undelayed short-circuit release
40 - 400A
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Rated permanent current Iu
160A
Rated voltage
220 - 690V
Integrated earth fault protection
No
Type of electrical connection of main circuit
Bolt connection
With under voltage release
No
Device construction
Built-in device fixed built-in technique
Number of poles
4
With switched-off indicator
No
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Degree of protection (IP)
IP20
Motor drive optional
Yes
Motor drive integrated
No
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
Yes
From same serie
1SDA068576R1 | XT4L 160 EKIP I IN=40A 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
- .. -A
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Adjustment range undelayed short-circuit release
40 .. 400A
Position of connection for main current circuit
Front side
Complete device with protection unit
Rated permanent current Iu
160A
Rated voltage
220 .. 690V
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
With under voltage release
Device construction
Built-in device fixed built-in technique
Number of poles
4
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Degree of protection (IP)
IP20
Motor drive optional
Motor drive integrated
Type of control element
Toggle
DIN rail (top hat rail) mounting optional
From same serie
We use cookies to enhance your experience.