Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
800A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
320.0 - 800A
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
With switched-off indicator
No
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
1000 - 10000A
Motor drive integrated
No
Motor drive optional
Yes
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
No
Type of control element
Toggle
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
0
Adjustment range short-term delayed short-circuit release
1000 - 10000A
Degree of protection (IP)
IP20
From same serie
1SDA069429R1 | T6V 800 PR221DS-I IN=800 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
800A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
320.0 .. 800A
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
With switched-off indicator
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
1000 .. 10000A
Motor drive integrated
Motor drive optional
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Type of control element
Toggle
Position of connection for main current circuit
Front side
Complete device with protection unit
Number of auxiliary contacts as change-over contact
0
Adjustment range short-term delayed short-circuit release
1000 .. 10000A
Degree of protection (IP)
IP20
From same serie