Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1200.0 - 9600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
480.0 - 7600A
Overload release current setting
320.0 - 800A
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
No
Integrated earth fault protection
No
Number of poles
4
With under voltage release
No
Degree of protection (IP)
IP20
Complete device with protection unit
Yes
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive optional
Yes
Motor drive integrated
No
From same serie
1SDA069434R1 | T6V 800 PR222DS/P-LSI IN=800 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1200.0 .. 9600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
480.0 .. 7600A
Overload release current setting
320.0 .. 800A
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
With switched-off indicator
Integrated earth fault protection
Number of poles
4
With under voltage release
Degree of protection (IP)
IP20
Complete device with protection unit
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive optional
Motor drive integrated
From same serie
We use cookies to enhance your experience.