Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
800A
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1200.0 - 12000A
DIN rail (top hat rail) mounting optional
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
170kA
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
No
Number of auxiliary contacts as change-over contact
0
Overload release current setting
320.0 - 800A
Type of electrical connection of main circuit
Bolt connection
Type of control element
Toggle
Number of poles
3
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Motor drive integrated
No
Motor drive optional
No
Complete device with protection unit
Yes
1SDA069449R1 | T7X 800 PR332/P LSIG In=800A 3p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
800A
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
DIN rail (top hat rail) mounting optional
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
170kA
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Number of auxiliary contacts as change-over contact
0
Overload release current setting
320.0 .. 800A
Type of electrical connection of main circuit
Bolt connection
Type of control element
Toggle
Number of poles
3
Degree of protection (IP)
IP20
Position of connection for main current circuit
Front side
Motor drive integrated
Motor drive optional
Complete device with protection unit