Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA069612R1 | XT4S 160 Ekip E-LSIG In=63A 3p F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
63 .. 630A
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
63 .. 630A
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
With under voltage release
Rated permanent current Iu
160A
Number of poles
3
Motor drive integrated
Motor drive optional
Rated voltage
220 .. 690V
Type of control element
Toggle
Degree of protection (IP)
IP20
Complete device with protection unit
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
DIN rail (top hat rail) mounting optional
Overload release current setting
25.2 .. 63A