Aleta.hr
Main Product Image

1SDA069634R1 | XT4L 160 Ekip E-LSIG In=160A 3p

Code: 1531141

ManufacturerABB
Catalog numberXT4L160E3
EAN code8015644703905

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
Overload release current setting64.0 - 160A
Rated voltage220 - 690V
Adjustment range undelayed short-circuit release160 - 1600A
DIN rail (top hat rail) mounting optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Number of poles3
Type of control elementToggle
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release160 - 1600A
With under voltage releaseNo
Device constructionBuilt-in device fixed built-in technique
Position of connection for main current circuitFront side
With switched-off indicatorNo
Degree of protection (IP)IP20
Motor drive optionalYes
Type of electrical connection of main circuitBolt connection
Complete device with protection unitYes
Rated permanent current Iu160A
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA069634R1 | XT4L 160 Ekip E-LSIG In=160A 3p

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Overload release current setting

64.0 .. 160A

Rated voltage

220 .. 690V

Adjustment range undelayed short-circuit release

160 .. 1600A

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Number of poles

3

Type of control element

Toggle

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

160 .. 1600A

With under voltage release

Device construction

Built-in device fixed built-in technique

Position of connection for main current circuit

Front side

With switched-off indicator

Degree of protection (IP)

IP20

Motor drive optional

Type of electrical connection of main circuit

Bolt connection

Complete device with protection unit

Rated permanent current Iu

160A

Motor drive integrated

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.