Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Built-in depth82.5mm
Rated current80A
Voltage typeAC
Rated voltage400V
Over voltage category3
Release characteristicKM
Number of protected poles3
Current limiting class3
Rated insulation voltage Ui690V
Degree of protection (IP)IP20
Frequency50 - 60Hz
Concurrently switching neutral conductorNo
Pollution degree4
Width in number of modular spacings3
Connectable conductor cross section multi-wired0 - 70mm²
Additional equipment possibleYes
Connectable conductor cross section solid-core0 - 50mm²
Ambient temperature during operating-25 - 60°C
Suitable for flush-mounted installationNo
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V40kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V50kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V50kA
Rated impulse withstand voltage Uimp8kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V40kA
Number of poles (total)3
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CCS863001R0626 | S803S-KM80

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Built-in depth

82.5mm

Rated current

80A

Voltage type

AC

Rated voltage

400V

Over voltage category

3

Release characteristic

KM

Number of protected poles

3

Current limiting class

3

Rated insulation voltage Ui

690V

Degree of protection (IP)

IP20

Frequency

50 .. 60Hz

Concurrently switching neutral conductor

Pollution degree

4

Width in number of modular spacings

3

Connectable conductor cross section multi-wired

0 .. 70mm²

Additional equipment possible

Connectable conductor cross section solid-core

0 .. 50mm²

Ambient temperature during operating

-25 .. 60°C

Suitable for flush-mounted installation

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

40kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

50kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

50kA

Rated impulse withstand voltage Uimp

8kV

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

40kA

Number of poles (total)

3

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.