Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Voltage typeAC
Rated voltage400V
Release characteristicC
Frequency50 - 60Hz
Rated insulation voltage Ui440V
Built-in depth69mm
Rated current25A
Current limiting class3
Degree of protection (IP)IP20
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V6kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V6kA
Number of poles (total)2
Concurrently switching neutral conductorNo
Additional equipment possibleNo
Connectable conductor cross section multi-wired0 - 25mm²
Over voltage category3
Flush-mounted installationNo
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V6kA
Power loss6.4W
Connectable conductor cross section solid-core0 - 25mm²
Explosion-proofNo
Suitable for flush-mounted installationNo
Width in number of modular spacings2
Pollution degree2
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V6kA
Ambient temperature during operating-25 - 55°C
Number of protected poles2
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CDS212001R0254 | SH202-C25

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Voltage type

AC

Rated voltage

400V

Release characteristic

C

Frequency

50 .. 60Hz

Rated insulation voltage Ui

440V

Built-in depth

69mm

Rated current

25A

Current limiting class

3

Degree of protection (IP)

IP20

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

6kA

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

6kA

Number of poles (total)

2

Concurrently switching neutral conductor

Additional equipment possible

Connectable conductor cross section multi-wired

0 .. 25mm²

Over voltage category

3

Flush-mounted installation

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

6kA

Power loss

6.4W

Connectable conductor cross section solid-core

0 .. 25mm²

Explosion-proof

Suitable for flush-mounted installation

Width in number of modular spacings

2

Pollution degree

2

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

6kA

Ambient temperature during operating

-25 .. 55°C

Number of protected poles

2

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.