2CDS253001R0205 | S203-B20
Code: 1549329

2CDS253001R0205 | S203-B20

Release characteristic
B
Number of protected poles
3
Rated current
20A
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
20kA
Additional equipment possible
Pollution degree
3
Suitable for flush-mounted installation
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
6kA
Rated voltage
400V
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
6kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
10kA
Current limiting class
3
Voltage type
AC
Rated impulse withstand voltage Uimp
4kV
Number of poles (total)
3
Frequency
50 .. 60Hz
Concurrently switching neutral conductor
Over voltage category
3
Rated insulation voltage Ui
440V
Degree of protection (IP)
IP20
Built-in depth
69mm
Connectable conductor cross section multi-wired
0 .. 25mm²
Width in number of modular spacings
3
Ambient temperature during operating
-25 .. 55°C
Connectable conductor cross section solid-core
0 .. 35mm²
Power loss
7.5W
Flush-mounted installation
Explosion-proof