Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Frequency50 - 60Hz
Built-in depth69mm
Rated insulation voltage Ui440V
Over voltage category3
Current limiting class3
Suitable for flush-mounted installationNo
Connectable conductor cross section solid-core0 - 35mm²
Pollution degree3
Degree of protection (IP)IP20
Ambient temperature during operating-25 - 55°C
Connectable conductor cross section multi-wired0 - 25mm²
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V10kA
Additional equipment possibleYes
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V10kA
Rated impulse withstand voltage Uimp4kV
Release characteristicK
Number of protected poles3
Number of poles (total)3
Rated current50A
Rated voltage400V
Voltage typeAC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V15kA
Concurrently switching neutral conductorNo
Width in number of modular spacings3
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CDS273001R0577 | S203M-K50

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Frequency

50 .. 60Hz

Built-in depth

69mm

Rated insulation voltage Ui

440V

Over voltage category

3

Current limiting class

3

Suitable for flush-mounted installation

Connectable conductor cross section solid-core

0 .. 35mm²

Pollution degree

3

Degree of protection (IP)

IP20

Ambient temperature during operating

-25 .. 55°C

Connectable conductor cross section multi-wired

0 .. 25mm²

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

10kA

Additional equipment possible

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

10kA

Rated impulse withstand voltage Uimp

4kV

Release characteristic

K

Number of protected poles

3

Number of poles (total)

3

Rated current

50A

Rated voltage

400V

Voltage type

AC

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

10kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

15kA

Concurrently switching neutral conductor

Width in number of modular spacings

3

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.