Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Rated insulation voltage Ui440V
Release characteristicC
Frequency50 - 60Hz
Rated current20A
Built-in depth69mm
Voltage typeAC/DC
Current limiting class3
Rated voltage400V
Over voltage category3
Width in number of modular spacings2
Concurrently switching neutral conductorNo
Suitable for flush-mounted installationNo
Connectable conductor cross section multi-wired0 - 16mm²
Flush-mounted installationNo
Power loss5.8W
Explosion-proofNo
Degree of protection (IP)IP20
Additional equipment possibleYes
Pollution degree3
Ambient temperature during operating-25 - 55°C
Number of protected poles2
Connectable conductor cross section solid-core0 - 25mm²
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V40kA
Number of poles (total)2
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V25kA
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V25kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V25kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CDS282001R0204 | S202P-C20

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • ABB

Technical specifications

Rated insulation voltage Ui

440V

Release characteristic

C

Frequency

50 .. 60Hz

Rated current

20A

Built-in depth

69mm

Voltage type

AC/DC

Current limiting class

3

Rated voltage

400V

Over voltage category

3

Width in number of modular spacings

2

Concurrently switching neutral conductor

Suitable for flush-mounted installation

Connectable conductor cross section multi-wired

0 .. 16mm²

Flush-mounted installation

Power loss

5.8W

Explosion-proof

Degree of protection (IP)

IP20

Additional equipment possible

Pollution degree

3

Ambient temperature during operating

-25 .. 55°C

Number of protected poles

2

Connectable conductor cross section solid-core

0 .. 25mm²

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

40kA

Number of poles (total)

2

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

25kA

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

25kA

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

25kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.