Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- ABB
Technical specifications
Rated insulation voltage Ui
440V
Rated impulse withstand voltage Uimp
4kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
12.5kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Suitable for flush-mounted installation
No
Release characteristic
C
Rated voltage
400V
Frequency
50 - 60Hz
Number of protected poles
4
Width in number of modular spacings
4
Additional equipment possible
Yes
Pollution degree
3
Over voltage category
3
Built-in depth
69mm
Number of poles (total)
4
Rated current
1.6A
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
25kA
Connectable conductor cross section solid-core
0 - 25mm²
Connectable conductor cross section multi-wired
0 - 16mm²
Ambient temperature during operating
-25 - 55°C
Current limiting class
3
Degree of protection (IP)
IP20
Concurrently switching neutral conductor
No
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
12.5kA
Voltage type
AC
Explosion-proof
No
Flush-mounted installation
No
Power loss
6.4W
2CDS284001R0974 | S204P-C1,6

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- ABB
Technical specifications
Rated insulation voltage Ui
440V
Rated impulse withstand voltage Uimp
4kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
12.5kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Suitable for flush-mounted installation
Release characteristic
C
Rated voltage
400V
Frequency
50 .. 60Hz
Number of protected poles
4
Width in number of modular spacings
4
Additional equipment possible
Pollution degree
3
Over voltage category
3
Built-in depth
69mm
Number of poles (total)
4
Rated current
1.6A
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
25kA
Connectable conductor cross section solid-core
0 .. 25mm²
Connectable conductor cross section multi-wired
0 .. 16mm²
Ambient temperature during operating
-25 .. 55°C
Current limiting class
3
Degree of protection (IP)
IP20
Concurrently switching neutral conductor
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
12.5kA
Voltage type
AC
Explosion-proof
Flush-mounted installation
Power loss
6.4W