Details
- •Earthing, lightning and surge protection
- •Lightning current arrester for power supply systems
- •1 KOM
- •ABB
Technical specifications
2CTB815101R1000 | OVR T1 1N 25-255 TS

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Earthing, lightning and surge protection
- Lightning current arrester for power supply systems
- 1 KOM
- ABB
Technical specifications
Mounting method
DIN rail (top hat rail) 35 mm
With remote signalling contact
Lightning impulse current (10/350 µs)
25kA
Number of conductors (without earthing)
2
Nominal voltage AC
230V
Degree of protection (IP)
IP20
System configuration TN-C
Max. conductor cross section solid (solid, stranded)
50mm²
Voltage protection level L-N
2.5kV
System configuration IT
Specific energy (W/R)
-kJ/Ohm
Max. continuous voltage AC
255V
Signalling at the device
None
Voltage protection level
2.5kV
System configuration TN-S
Suitable for outdoor use
Integrated backup fuse
Nominal discharge surge current (8/20)
25kA
Max. conductor cross section flexible (fine-strand)
35mm²
System configuration TN
Construction size
4 modular spacing
System configuration TN-C-S
Voltage protection level N-PE
2.5kV
System configuration DC
System configuration TT
Exhausting
Follow current extinguishing capability
50kA
System configuration other
Category type 1