Technical specifications

Construction size4 modular spacing
Mounting methodDIN rail (top hat rail) 35 mm
Number of conductors (without earthing)2
With remote signalling contactNo
Voltage protection level2.5kV
Lightning impulse current (10/350 µs)25kA
Suitable for outdoor useNo
ExhaustingNo
System configuration DCNo
Voltage protection level L-N2.5kV
Degree of protection (IP)IP20
System configuration ITNo
Max. conductor cross section solid (solid, stranded)50mm²
Signalling at the deviceNone
Nominal voltage AC230V
Follow current extinguishing capability50kA
System configuration TTNo
Nominal discharge surge current (8/20)25kA
System configuration TN-CYes
Category type 1Yes
Max. conductor cross section flexible (fine-strand)35mm²
System configuration TNNo
Integrated backup fuseNo
System configuration TN-SYes
Specific energy (W/R)-kJ/Ohm
System configuration otherNo
System configuration TN-C-SNo
Voltage protection level N-PE2.5kV
Max. continuous voltage AC255V
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CTB815101R1200 | OVR T1 2L 25-255

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Earthing, lightning and surge protection
  • Lightning current arrester for power supply systems
  • 1 KOM
  • ABB

Technical specifications

Construction size

4 modular spacing

Mounting method

DIN rail (top hat rail) 35 mm

Number of conductors (without earthing)

2

With remote signalling contact

Voltage protection level

2.5kV

Lightning impulse current (10/350 µs)

25kA

Suitable for outdoor use

Exhausting

System configuration DC

Voltage protection level L-N

2.5kV

Degree of protection (IP)

IP20

System configuration IT

Max. conductor cross section solid (solid, stranded)

50mm²

Signalling at the device

None

Nominal voltage AC

230V

Follow current extinguishing capability

50kA

System configuration TT

Nominal discharge surge current (8/20)

25kA

System configuration TN-C

Category type 1

Max. conductor cross section flexible (fine-strand)

35mm²

System configuration TN

Integrated backup fuse

System configuration TN-S

Specific energy (W/R)

-kJ/Ohm

System configuration other

System configuration TN-C-S

Voltage protection level N-PE

2.5kV

Max. continuous voltage AC

255V