Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
4000A
Overload release current setting
1600.0 - 4000A
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
With switched-off indicator
Yes
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Adjustment range undelayed short-circuit release
6000.0 - 60000A
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
2400.0 - 2400.0A
Type of control element
Push button
Motor drive integrated
No
Integrated earth fault protection
Yes
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Bolt connection
From same serie
1SDA055527R1 | E4H/F 4000 PR123/P-LSIG IN=4000A 4P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
4000A
Overload release current setting
1600.0 .. 4000A
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
With switched-off indicator
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
2400.0 .. 2400.0A
Type of control element
Push button
Motor drive integrated
Integrated earth fault protection
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Bolt connection
From same serie