Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Integrated earth fault protection
Yes
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Adjustment range short-term delayed short-circuit release
2400.0 - 2400.0A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
With under voltage release
No
Overload release current setting
1600.0 - 4000A
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
Yes
Complete device with protection unit
Yes
Type of control element
Push button
Motor drive integrated
No
Degree of protection (IP)
IP30
Number of poles
4
1SDA055535R1 | E4H/F 4000 PR123/P-LSIG IN=4000A 4P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Integrated earth fault protection
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Adjustment range short-term delayed short-circuit release
2400.0 .. 2400.0A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
With under voltage release
Overload release current setting
1600.0 .. 4000A
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
Complete device with protection unit
Type of control element
Push button
Motor drive integrated
Degree of protection (IP)
IP30
Number of poles
4
We use cookies to enhance your experience.