Technical specifications

Rated permanent current Iu4000A
Overload release current setting1600.0 - 4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz80kA
Type of electrical connection of main circuitConnection at separate chassis part
Integrated earth fault protectionYes
Adjustment range short-term delayed short-circuit release4000 - 40000A
Adjustment range undelayed short-circuit release6000.0 - 60000A
Rated voltage690 - 690V
Suitable for DIN rail (top hat rail) mountingNo
Number of poles4
Position of connection for main current circuitConnection at separate chassis part
With under voltage releaseNo
Number of auxiliary contacts as change-over contact4
Motor drive optionalYes
Degree of protection (IP)IP30
Motor drive integratedNo
Type of control elementPush button
Complete device with protection unitYes
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055546R1 | E4S/F 4000 PR121/P-LSIG IN=4000A 4P

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

4000A

Overload release current setting

1600.0 .. 4000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

80kA

Type of electrical connection of main circuit

Connection at separate chassis part

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

4000 .. 40000A

Adjustment range undelayed short-circuit release

6000.0 .. 60000A

Rated voltage

690 .. 690V

Suitable for DIN rail (top hat rail) mounting

Number of poles

4

Position of connection for main current circuit

Connection at separate chassis part

With under voltage release

Number of auxiliary contacts as change-over contact

4

Motor drive optional

Degree of protection (IP)

IP30

Motor drive integrated

Type of control element

Push button

Complete device with protection unit

With switched-off indicator

DIN rail (top hat rail) mounting optional

Device construction

Built-in device slide-in technique (withdrawable)

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.