Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles4
Rated permanent current Iu6300A
Overload release current setting2520.0 - 6300A
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
With under voltage releaseNo
Adjustment range undelayed short-circuit release9450.0 - 94500A
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Motor drive optionalYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
Adjustment range short-term delayed short-circuit release6300 - 63000A
With switched-off indicatorYes
Integrated earth fault protectionNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055592R1 | E6H/F 6300 PR121/P-LI IN=6300A 4P W

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

4

Rated permanent current Iu

6300A

Overload release current setting

2520.0 .. 6300A

Position of connection for main current circuit

Connection at separate chassis part

Motor drive integrated

Degree of protection (IP)

IP30

Number of auxiliary contacts as change-over contact

4

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

With under voltage release

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Complete device with protection unit

Motor drive optional

Device construction

Built-in device slide-in technique (withdrawable)

Type of electrical connection of main circuit

Connection at separate chassis part

Type of control element

Push button

Adjustment range short-term delayed short-circuit release

6300 .. 63000A

With switched-off indicator

Integrated earth fault protection