Technical specifications

Rated permanent current Iu800A
Rated voltage690 - 690V
Overload release current setting320.0 - 800A
Type of electrical connection of main circuitBolt connection
DIN rail (top hat rail) mounting optionalNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Number of auxiliary contacts as normally closed contact0
Adjustment range short-term delayed short-circuit release800 - 8000A
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release1200.0 - 12000A
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorYes
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Number of poles4
Motor drive integratedNo
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
Motor drive optionalYes
Complete device with protection unitYes
Type of control elementPush button
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055608R1 | E1B 800 PR121/P-LI IN=800A 4P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

800A

Rated voltage

690 .. 690V

Overload release current setting

320.0 .. 800A

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

Number of auxiliary contacts as normally closed contact

0

Adjustment range short-term delayed short-circuit release

800 .. 8000A

Device construction

Built-in device fixed built-in technique

Integrated earth fault protection

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Suitable for DIN rail (top hat rail) mounting

With switched-off indicator

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Number of poles

4

Motor drive integrated

Degree of protection (IP)

IP30

Position of connection for main current circuit

Back side

Motor drive optional

Complete device with protection unit

Type of control element

Push button

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.