Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles4
Number of auxiliary contacts as change-over contact4
Rated permanent current Iu800A
Number of auxiliary contacts as normally closed contact0
Overload release current setting320.0 - 800A
Rated voltage690 - 690V
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release1200.0 - 12000A
Motor drive integratedNo
Degree of protection (IP)IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Adjustment range short-term delayed short-circuit release480.0 - 480.0A
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
Position of connection for main current circuitConnection at separate chassis part
Type of control elementPush button
Motor drive optionalYes
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055628R1 | E1B 800 PR122/P-LSI IN=800A 4P W MP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

4

Number of auxiliary contacts as change-over contact

4

Rated permanent current Iu

800A

Number of auxiliary contacts as normally closed contact

0

Overload release current setting

320.0 .. 800A

Rated voltage

690 .. 690V

Number of auxiliary contacts as normally open contact

0

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Motor drive integrated

Degree of protection (IP)

IP30

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

Adjustment range short-term delayed short-circuit release

480.0 .. 480.0A

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

With switched-off indicator

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Motor drive optional

Complete device with protection unit

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.