Technical specifications

Rated permanent current Iu1250A
Overload release current setting500.0 - 1250A
Rated voltage690 - 690V
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release750.0 - 750.0A
Adjustment range undelayed short-circuit release1875.0 - 18750A
Type of electrical connection of main circuitBolt connection
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact0
DIN rail (top hat rail) mounting optionalNo
Number of auxiliary contacts as normally open contact0
Type of control elementPush button
With switched-off indicatorYes
Position of connection for main current circuitBack side
Number of poles4
Motor drive integratedNo
Degree of protection (IP)IP30
Motor drive optionalYes
Complete device with protection unitYes
Number of auxiliary contacts as change-over contact4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055643R1 | E1B 1250 PR122/P-LI IN=1250A 4P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

1250A

Overload release current setting

500.0 .. 1250A

Rated voltage

690 .. 690V

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

750.0 .. 750.0A

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally closed contact

0

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally open contact

0

Type of control element

Push button

With switched-off indicator

Position of connection for main current circuit

Back side

Number of poles

4

Motor drive integrated

Degree of protection (IP)

IP30

Motor drive optional

Complete device with protection unit

Number of auxiliary contacts as change-over contact

4

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA