Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage690 - 690V
Adjustment range short-term delayed short-circuit release960.0 - 960.0A
Integrated earth fault protectionYes
Device constructionBuilt-in device fixed built-in technique
Rated permanent current Iu1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Adjustment range undelayed short-circuit release2400.0 - 24000A
Overload release current setting640.0 - 1600A
DIN rail (top hat rail) mounting optionalNo
Type of electrical connection of main circuitBolt connection
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitBack side
Number of poles3
Type of control elementPush button
Motor drive integratedNo
With switched-off indicatorYes
Motor drive optionalYes
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055671R1 | E1B 1600 PR123/P-LSIG IN=1600A 3P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

690 .. 690V

Adjustment range short-term delayed short-circuit release

960.0 .. 960.0A

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

Rated permanent current Iu

1600A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Overload release current setting

640.0 .. 1600A

DIN rail (top hat rail) mounting optional

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally closed contact

0

Position of connection for main current circuit

Back side

Number of poles

3

Type of control element

Push button

Motor drive integrated

With switched-off indicator

Motor drive optional

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.