Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
1600 - 16000A
Overload release current setting
640.0 - 1600A
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Complete device with protection unit
Yes
Integrated earth fault protection
Yes
Motor drive optional
Yes
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
With under voltage release
No
Type of control element
Push button
Motor drive integrated
No
Degree of protection (IP)
IP30
From same serie
1SDA055682R1 | E1B 1600 PR121/P-LSIG IN=1600A 3P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Overload release current setting
640.0 .. 1600A
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Complete device with protection unit
Integrated earth fault protection
Motor drive optional
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
With under voltage release
Type of control element
Push button
Motor drive integrated
Degree of protection (IP)
IP30