Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA055693R1 | E1B 1600 PR122/P-LSIG IN=1600A 4P W MP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Degree of protection (IP)
IP30
Adjustment range short-term delayed short-circuit release
960.0 .. 960.0A
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Overload release current setting
640.0 .. 1600A
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
4
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Type of control element
Push button
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive integrated
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Complete device with protection unit
Device construction
Built-in device slide-in technique (withdrawable)
Rated permanent current Iu
1600A