1SDA055762R1 | E1N 1600 PR121/P-LSIG IN=1600A 3P F HR
Code: 1592349

1SDA055762R1 | E1N 1600 PR121/P-LSIG IN=1600A 3P F HR

Rated permanent current Iu
1600A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Overload release current setting
640.0 .. 1600A
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Motor drive integrated
With switched-off indicator
Degree of protection (IP)
IP30
Complete device with protection unit
Motor drive optional
Number of poles
3
Integrated earth fault protection
Position of connection for main current circuit
Back side