Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles4
Rated permanent current Iu1600A
Overload release current setting640.0 - 1600A
Number of auxiliary contacts as change-over contact4
Rated voltage690 - 690V
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Type of control elementPush button
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Adjustment range short-term delayed short-circuit release960.0 - 960.0A
Adjustment range undelayed short-circuit release2400.0 - 24000A
Integrated earth fault protectionYes
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorYes
Motor drive optionalYes
With under voltage releaseNo
Complete device with protection unitYes
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055807R1 | E2B 1600 PR123/P-LSIG IN=1600A 4P F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

4

Rated permanent current Iu

1600A

Overload release current setting

640.0 .. 1600A

Number of auxiliary contacts as change-over contact

4

Rated voltage

690 .. 690V

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

Type of control element

Push button

Degree of protection (IP)

IP30

Position of connection for main current circuit

Back side

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

Adjustment range short-term delayed short-circuit release

960.0 .. 960.0A

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

With switched-off indicator

Motor drive optional

With under voltage release

Complete device with protection unit

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.