Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated permanent current Iu
1600A
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
No
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
640.0 - 1600A
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Rated voltage
690 - 690V
Complete device with protection unit
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive optional
Yes
Adjustment range short-term delayed short-circuit release
1600 - 16000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
1SDA055816R1 | E2B 1600 PR121/P-LI IN=1600A 4P W M

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated permanent current Iu
1600A
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
With switched-off indicator
DIN rail (top hat rail) mounting optional
Motor drive integrated
Number of auxiliary contacts as normally closed contact
0
Overload release current setting
640.0 .. 1600A
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Rated voltage
690 .. 690V
Complete device with protection unit
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive optional
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA