Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu2000A
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Number of poles4
With switched-off indicatorYes
Overload release current setting800.0 - 2000A
Degree of protection (IP)IP30
Adjustment range short-term delayed short-circuit release1200.0 - 1200.0A
Position of connection for main current circuitBack side
Motor drive optionalYes
Type of control elementPush button
Type of electrical connection of main circuitBolt connection
Adjustment range undelayed short-circuit release3000.0 - 30000A
Motor drive integratedNo
DIN rail (top hat rail) mounting optionalNo
Rated voltage690 - 690V
Integrated earth fault protectionYes
Number of auxiliary contacts as change-over contact4
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055839R1 | E2B 2000 PR123/P-LSIG IN=2000A 4P F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

2000A

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Number of poles

4

With switched-off indicator

Overload release current setting

800.0 .. 2000A

Degree of protection (IP)

IP30

Adjustment range short-term delayed short-circuit release

1200.0 .. 1200.0A

Position of connection for main current circuit

Back side

Motor drive optional

Type of control element

Push button

Type of electrical connection of main circuit

Bolt connection

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

Motor drive integrated

DIN rail (top hat rail) mounting optional

Rated voltage

690 .. 690V

Integrated earth fault protection

Number of auxiliary contacts as change-over contact

4

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.