Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu1600A
Overload release current setting640.0 - 1600A
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Number of poles4
Rated voltage690 - 690V
Number of auxiliary contacts as change-over contact4
With under voltage releaseNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Type of control elementPush button
DIN rail (top hat rail) mounting optionalNo
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Motor drive optionalYes
Adjustment range undelayed short-circuit release2400.0 - 24000A
Type of electrical connection of main circuitConnection at separate chassis part
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release960.0 - 960.0A
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055915R1 | E2N 1600 PR122/P-LI IN=1600A 4P W MP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

1600A

Overload release current setting

640.0 .. 1600A

Position of connection for main current circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Number of poles

4

Rated voltage

690 .. 690V

Number of auxiliary contacts as change-over contact

4

With under voltage release

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Type of control element

Push button

DIN rail (top hat rail) mounting optional

Motor drive integrated

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Device construction

Built-in device slide-in technique (withdrawable)

Motor drive optional

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Type of electrical connection of main circuit

Connection at separate chassis part

With switched-off indicator

Adjustment range short-term delayed short-circuit release

960.0 .. 960.0A

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.