Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA055932R1 | E2N 2000 PR122/P-LSI IN=2000A 4P F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
2000A
Number of auxiliary contacts as change-over contact
4
Overload release current setting
800.0 .. 2000A
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Number of poles
4
With switched-off indicator
Type of electrical connection of main circuit
Bolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
1200.0 .. 1200.0A
Position of connection for main current circuit
Back side
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30
Motor drive integrated
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Motor drive optional
With under voltage release
Complete device with protection unit