Suitable for DIN rail (top hat rail) mountingNo
Rated permanent current Iu2000A
Number of auxiliary contacts as change-over contact4
Overload release current setting800.0 - 2000A
Adjustment range undelayed short-circuit release3000.0 - 30000A
Number of poles4
With switched-off indicatorYes
Type of electrical connection of main circuitBolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
Type of control elementPush button
Adjustment range short-term delayed short-circuit release1200.0 - 1200.0A
Position of connection for main current circuitBack side
Rated voltage690 - 690V
Degree of protection (IP)IP30
Motor drive integratedNo
DIN rail (top hat rail) mounting optionalNo
Integrated earth fault protectionNo
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
With under voltage releaseNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055932R1 | E2N 2000 PR122/P-LSI IN=2000A 4P F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Suitable for DIN rail (top hat rail) mounting

Rated permanent current Iu

2000A

Number of auxiliary contacts as change-over contact

4

Overload release current setting

800.0 .. 2000A

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

Number of poles

4

With switched-off indicator

Type of electrical connection of main circuit

Bolt connection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

Type of control element

Push button

Adjustment range short-term delayed short-circuit release

1200.0 .. 1200.0A

Position of connection for main current circuit

Back side

Rated voltage

690 .. 690V

Degree of protection (IP)

IP30

Motor drive integrated

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

Motor drive optional

With under voltage release

Complete device with protection unit