Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 - 690V
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Rated permanent current Iu
2000A
Number of auxiliary contacts as normally open contact
0
Overload release current setting
800.0 - 2000A
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Adjustment range short-term delayed short-circuit release
1200.0 - 1200.0A
With switched-off indicator
Yes
Device construction
Built-in device slide-in technique (withdrawable)
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Motor drive optional
Yes
Motor drive integrated
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Type of control element
Push button
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
1SDA055949R1 | E2N 2000 PR122/P-LSIG IN=2000A 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
690 .. 690V
Integrated earth fault protection
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
2000A
Number of auxiliary contacts as normally open contact
0
Overload release current setting
800.0 .. 2000A
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Adjustment range short-term delayed short-circuit release
1200.0 .. 1200.0A
With switched-off indicator
Device construction
Built-in device slide-in technique (withdrawable)
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Motor drive integrated
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
65kA
Type of control element
Push button
Number of auxiliary contacts as normally closed contact
0
Degree of protection (IP)
IP30
Complete device with protection unit
We use cookies to enhance your experience.