Aleta.hr
Main Product Image

1SDA055957R1 | E2S 1250 PR122/P-LSIG IN=1250A 3P F HR

Code: 1592544

ManufacturerABB
Catalog number1SDA055957R1
EAN code8015644572976

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release750.0 - 750.0A
Rated voltage690 - 690V
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Rated permanent current Iu1250A
Number of auxiliary contacts as change-over contact4
Position of connection for main current circuitBack side
Integrated earth fault protectionYes
Adjustment range undelayed short-circuit release1875.0 - 18750A
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitBolt connection
Number of poles3
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Complete device with protection unitYes
Motor drive optionalYes
Degree of protection (IP)IP30
Motor drive integratedNo
Overload release current setting500.0 - 1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Type of control elementPush button
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055957R1 | E2S 1250 PR122/P-LSIG IN=1250A 3P F HR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release

750.0 .. 750.0A

Rated voltage

690 .. 690V

With switched-off indicator

DIN rail (top hat rail) mounting optional

Rated permanent current Iu

1250A

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Back side

Integrated earth fault protection

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Bolt connection

Number of poles

3

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Complete device with protection unit

Motor drive optional

Degree of protection (IP)

IP30

Motor drive integrated

Overload release current setting

500.0 .. 1250A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Type of control element

Push button

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.