Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
750.0 - 750.0A
Overload release current setting
500.0 - 1250A
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
1875.0 - 18750A
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Yes
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
No
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
Number of poles
4
Type of control element
Push button
Position of connection for main current circuit
Back side
Motor drive integrated
No
With under voltage release
No
Rated voltage
690 - 690V
1SDA055964R1 | E2S 1250 PR122/P-LSI IN=1250A 4P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
750.0 .. 750.0A
Overload release current setting
500.0 .. 1250A
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP30
Number of poles
4
Type of control element
Push button
Position of connection for main current circuit
Back side
Motor drive integrated
With under voltage release
Rated voltage
690 .. 690V