Rated permanent current Iu1600A
Number of auxiliary contacts as change-over contact4
Type of electrical connection of main circuitBolt connection
Overload release current setting640.0 - 1600A
With switched-off indicatorYes
Number of poles3
Integrated earth fault protectionYes
Motor drive integratedNo
Adjustment range short-term delayed short-circuit release960.0 - 960.0A
Degree of protection (IP)IP30
Motor drive optionalYes
Position of connection for main current circuitBack side
Type of control elementPush button
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release2400.0 - 24000A
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Rated voltage690 - 690V
Device constructionBuilt-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055989R1 | E2S 1600 PR122/P-LSIG IN=1600A 3P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

1600A

Number of auxiliary contacts as change-over contact

4

Type of electrical connection of main circuit

Bolt connection

Overload release current setting

640.0 .. 1600A

With switched-off indicator

Number of poles

3

Integrated earth fault protection

Motor drive integrated

Adjustment range short-term delayed short-circuit release

960.0 .. 960.0A

Degree of protection (IP)

IP30

Motor drive optional

Position of connection for main current circuit

Back side

Type of control element

Push button

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

With under voltage release

DIN rail (top hat rail) mounting optional

Rated voltage

690 .. 690V

Device construction

Built-in device fixed built-in technique

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Complete device with protection unit