  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Adjustment range undelayed short-circuit release2400.0 - 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Suitable for DIN rail (top hat rail) mountingNo
Number of poles3
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
Integrated earth fault protectionYes
Device constructionBuilt-in device fixed built-in technique
Overload release current setting640.0 - 1600A
Rated permanent current Iu1600A
Adjustment range short-term delayed short-circuit release960.0 - 960.0A
Type of control elementPush button
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Rated voltage690 - 690V
Motor drive optionalYes
Complete device with protection unitYes
Position of connection for main current circuitBack side
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055991R1 | E2S 1600 PR123/P-LSIG IN=1600A 3P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Suitable for DIN rail (top hat rail) mounting

Number of poles

3

DIN rail (top hat rail) mounting optional

With switched-off indicator

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

Overload release current setting

640.0 .. 1600A

Rated permanent current Iu

1600A

Adjustment range short-term delayed short-circuit release

960.0 .. 960.0A

Type of control element

Push button

Degree of protection (IP)

IP30

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Rated voltage

690 .. 690V

Motor drive optional

Complete device with protection unit

Position of connection for main current circuit

Back side

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.