Technical specifications

Rated voltage690 - 690V
Rated permanent current Iu1600A
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device fixed built-in technique
With switched-off indicatorYes
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release1600 - 16000A
Position of connection for main current circuitBack side
Number of auxiliary contacts as change-over contact4
Type of electrical connection of main circuitBolt connection
Integrated earth fault protectionYes
Type of control elementPush button
Complete device with protection unitYes
Motor drive integratedNo
Number of poles4
Adjustment range undelayed short-circuit release2400.0 - 24000A
With under voltage releaseNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Overload release current setting640.0 - 1600A
Motor drive optionalYes
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA055994R1 | E2S 1600 PR121/P-LSIG IN=1600A 4P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

690 .. 690V

Rated permanent current Iu

1600A

DIN rail (top hat rail) mounting optional

Device construction

Built-in device fixed built-in technique

With switched-off indicator

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

1600 .. 16000A

Position of connection for main current circuit

Back side

Number of auxiliary contacts as change-over contact

4

Type of electrical connection of main circuit

Bolt connection

Integrated earth fault protection

Type of control element

Push button

Complete device with protection unit

Motor drive integrated

Number of poles

4

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

With under voltage release

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Overload release current setting

640.0 .. 1600A

Motor drive optional

Degree of protection (IP)

IP30