Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of poles4
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu2000A
Type of electrical connection of main circuitBolt connection
Position of connection for main current circuitBack side
Rated voltage690 - 690V
Degree of protection (IP)IP30
Type of control elementPush button
Overload release current setting800.0 - 2000A
Number of auxiliary contacts as change-over contact4
Motor drive integratedNo
With switched-off indicatorYes
Adjustment range undelayed short-circuit release3000.0 - 30000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release1200.0 - 1200.0A
Integrated earth fault protectionNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA056027R1 | E2S 2000 PR122/P-LI IN=2000A 4P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

2000A

Type of electrical connection of main circuit

Bolt connection

Position of connection for main current circuit

Back side

Rated voltage

690 .. 690V

Degree of protection (IP)

IP30

Type of control element

Push button

Overload release current setting

800.0 .. 2000A

Number of auxiliary contacts as change-over contact

4

Motor drive integrated

With switched-off indicator

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

DIN rail (top hat rail) mounting optional

Motor drive optional

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

1200.0 .. 1200.0A

Integrated earth fault protection

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.