Aleta.hr
Main Product Image

1SDA056029R1 | E2S 2000 PR122/P-LSIG IN=2000A 4P F HR

Code: 1592616

ManufacturerRAZNO
Catalog number1SDA056029R1
Type
EAN code8015644573690

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

2000A

Rated voltage

690 - 690V

Integrated earth fault protection

Yes

Adjustment range undelayed short-circuit release

3000.0 - 30000A

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

No

Number of auxiliary contacts as normally closed contact

0

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

DIN rail (top hat rail) mounting optional

No

Position of connection for main current circuit

Back side

Overload release current setting

800.0 - 2000A

Number of auxiliary contacts as change-over contact

4

Motor drive integrated

No

Adjustment range short-term delayed short-circuit release

1200.0 - 1200.0A

Degree of protection (IP)

IP30

Type of electrical connection of main circuit

Bolt connection

Type of control element

Push button

With switched-off indicator

Yes

Complete device with protection unit

Yes

Motor drive optional

Yes

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA056029R1 | E2S 2000 PR122/P-LSIG IN=2000A 4P F HR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

2000A

Rated voltage

690 .. 690V

Integrated earth fault protection

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally closed contact

0

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

DIN rail (top hat rail) mounting optional

Position of connection for main current circuit

Back side

Overload release current setting

800.0 .. 2000A

Number of auxiliary contacts as change-over contact

4

Motor drive integrated

Adjustment range short-term delayed short-circuit release

1200.0 .. 1200.0A

Degree of protection (IP)

IP30

Type of electrical connection of main circuit

Bolt connection

Type of control element

Push button

With switched-off indicator

Complete device with protection unit

Motor drive optional

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.